MODEL | AP610 | AP615 | AP620 | AP630 |
Elevator motor | 2.2kW | 3.3kW | 5.5KW | 7.5kW-9KW |
Display |
Indicator on Panel | LED / LCD plus LED display |
AC MODE |
Input Voltage | 165Vac ~ 275Vac / 150Vac-275Vac(optional) |
Input Frequency | 45-65 Hz( transfer to battery mode if out of this range) |
Output voltage | 220Vac± 10% |
Efficiency | ≥ 96% (AC Mode) |
Overload in AC mode | 110% transfer to bypass within 60sec; |
120% transfer to bypass within 30sec; |
Automatic recovery if load capacity is restored to normal. |
Short Circuit | Protected by Input Fuse |
INVERTER MODE |
Output Voltage | 220Vac± 5% |
Output Frequency | 50HZ/60HZ ± 1% self-detection |
Output P.F | ≥0.6 |
Waveform Distortion | Liner Load ≤ 5% |
Battery Backup Time | ≥ 10min (PC load) |
Transfer Time | Typical value 5ms, Max: 8ms |
Efficiency | ≥ 80(INV Mode) |
Overload in INV mode | 110% Shut down within 60sec; |
120% Shut down within 5sec; |
Short Circuit | ≥20ms System shut down automatically |
ALARM |
AC abnormal | Once every 4sec, be silent after 40s |
Battery low | Once every 0.2sec |
Overload | Once every 1sec |
Battery |
DC voltage | 24V | 24V | 24V | 48V |
Configuration | 2×12V 9AH | 2×12V 9AH | 4×12V 9AH | 4×12V 9AH |
Charging current | 1.2A(Max.) |
Recharge Time | 90% Capacity after 8hours |
Communication (option) | RS232/USB/SNMP(can be set to turn on/off UPS automatically) |
OTHERS |
Output Sockets | Customized upon request |
IP Level | IP20 |
Ambient Temperature | 0℃ ~ 40℃ |
Ambient Humidity | 10% ~ 90% (No Condensing) |
Noise | ≤50dB (1m) |
Dimension (mm)D*W*H | 360×145×215 | 430×145×215 | 475×200×337 |
Packing Dimension(mm) | 450×325×245 | 430×145×215 | 590×320×465 |
Net Weight (kg) | 14.5 | 15.5 | 20.5 | 27.5 |
Gross Weight (kg) | 15.5 | 16.5 | 21.5 | 28.6 |